Basic Info

ItemSpecificationItemSpecification
Model NO.YKS710-4-7000KW-6KVNumber of StatorThree-Phase
Rotor StructureSquirrel-CageCasing ProtectionClosed Type
Number of Poles2p-16pStarting ModeDirect on-line Starting
CertificationISO9001, CCC, CERated Power4000kw
Frequency50Hz/60HzVoltage6kv, 6.6kv, 10kv, 11kv, 13.2kv, 13.8kv
ProtectionIP54Cooling MethodIC81W
MountingIMB3Rotation DirectionBoth
InsulationF ClassColorCustomizable
Duty TypeS1StandardIEC
Temperature RiseB ClassAmbient TemperatureMax 40℃
Altitude Above Sea Level≤1000mBearingSKF Bearing
Transport PackageStandard Seaworthy PackingTrademarkCHANGLI
OriginChinaHS Code8501530090
Production Capacity500000 sets per year--

Product Description

Y, YKS, YQF, YKK, YR, YRKS, YRQF and YRKK series high voltage three-phase induction motors were introduced and developed by our company back in the 1980s, with more than 30 years of development history. In recent years, continuous upgrades of insulation materials, adoption of low-loss silicon steel sheets, grade upgrades and design optimization effectively cut motor losses and increase power capacity. Drawing on our 60 years of experience in high voltage induction motor design and manufacturing, we completed the latest round of optimization to meet domestic and industrial market demands. Test results show that this new series reaches or approaches global advanced levels in both technical and economic performance. The motors are mass-produced and exported to over 20 countries and regions including Europe, America, Africa, Hong Kong and Macao, and widely used across China, earning consistent positive feedback from end users.

Manufactured with premium raw materials and mature production processes, this motor series features high efficiency, energy saving, low vibration, stable operation and simple installation and maintenance.

Power grades, electrical performance, mounting dimensions and tolerances comply with GB755 Rotating Electric Machines – Ratings and Performance, IEC 60034-1 Rotating Electric Machines – Ratings and Performance and relevant machinery industry standards.

In accordance with GB4942.1 and IEC 60034-5, the enclosure protection grades available include IP23, IP44, IP54, IP55 and IP56. IP23 motors can be converted to IP44 (piped ventilation) or IPW24 (weather protected type). Custom protection grades are available upon request.

Cooling types follow GB/T1993 and IEC 60034-6, covering IC01, IC611 and IC81W. Other cooling configurations can be supplied as required.

The standard construction and mounting form is IMB3 (horizontal foot-mounted), conforming to GB997 and IEC 60034-7.

The series is divided into 8 sub-models based on rotor type, protection class and cooling method:

ModelProtection ClassCooling MethodSquirrel Cage RotorWound Rotor
Weather ProtectedIP23IC01Y SeriesYR Series
Climate Protection TypeIPW24IC01YQF SeriesYRQF Series
Air-Water Cooled EnclosedIP44, IP54, IP55, IP56IC81WYKS SeriesYRKS Series
Air-Air Cooled EnclosedIP44, IP54, IP55, IP56IC611YKK SeriesYRKK Series

Technical data and installation dimensions of 10kV motors in this range can be adapted for 3kV, 10.5kV and 11kV versions of the same frame size.

Application

This motor series drives general equipment such as compressors, fans, water pumps, feeders and conveyors. It serves as the prime mover for mines, machinery plants, petrochemical facilities, power plants and other industrial and mining sites.
For heavy inertia loads including blowers, coal mills, rolling mills, crushers and belt conveyors, customers shall provide complete technical data and sign a technical agreement for customized design to guarantee reliable operation.

Normal Operating Conditions

  • Altitude: ≤1000m above sea level
  • Max ambient temperature: ≤40℃; minimum ambient temperature: -15℃ for rolling bearing motors, 5℃ for sliding bearing motors; YKS / YRKS minimum ambient temperature: 5℃
  • For YKS and YRKS: cooling water inlet temperature 5℃ ~ 33℃
  • Average maximum relative humidity 90% in damp months, with average minimum temperature ≤25℃
  • Power frequency: 50Hz±1%
  • Supply voltage fluctuation: within ±5% of rated voltage
  • Duty: S1 continuous operation

Construction Description

Y and YR are the base models with IP23 protection and IC01 cooling. Derivative types include YKS (air-water cooling), YQF (weather protected), YKK (air-air cooling), YRKS, YRQF and YRKK.

The motor adopts internationally popular box-type construction. Frame and end shields are steel plate welded for high rigidity and low weight. Cooler or protective cover can be removed for easy inspection, installation and maintenance.
The stator uses outer pressing structure. Stator windings adopt F-class insulation and anti-corona materials, with reliable special binding for terminal fixing. The whole stator goes through VPI vacuum pressure impregnation with solventless F-class varnish, delivering outstanding insulation, moisture resistance and shock resistance.

Most squirrel cage rotors are cast aluminum type for reliable operation without rotor bar breakage. Copper bar squirrel cage rotors use advanced welding and slot fastening technology. Wound rotors are fitted with F-class insulation and also treated by VPI.

Bearings are either rolling bearings or sliding bearings, selected according to motor power and speed. Base bearing protection grade is IP44 and will be upgraded for higher enclosure protection requirements.
Rolling bearing version is equipped with on-line oil filling and draining structure, allowing lubrication maintenance without shutdown.

The main terminal box is sealed at IP54. It is mounted on the right side (viewed from shaft extension) and can be switched to the left side on request. Cable entry direction can be adjusted to top, bottom, left or right. Independent grounding terminal is built inside the box.

Starting Instruction for Y, YKS, YQF, YKK Induction Motors

Rotor thermal and stress simulation is completed by computer calculation to avoid early damage caused by overheating during startup. Please follow the requirements below:

  • The total inertia of driven equipment (converted to motor speed) shall not exceed the allowable load inertia listed in technical data sheet
  • The terminal voltage during starting shall be no less than 85% of rated voltage
  • Load torque characteristic shall match typical fan and pump curve

Under above conditions, the motor allows two consecutive cold starts or one hot start, with natural coast-down between attempts. Extra restart attempts require a 1-hour waiting period.
Contact us for customized design if driven inertia exceeds the limit, frequent starting or heavy-load startup is required.

Certifications

ISO9001, CCC, CE

Packaging & Shipping

Standard seaworthy export packing
Available power range: 0.55KW ~20000KW
Available voltage range: 380V ~13.8KV
Shaft height: 80mm ~1120mm

Our Advantages

  • Wide power coverage
  • Superior starting performance
  • Suitable for global industrial sectors and diverse working conditions
  • High reliability to cut downtime and operating cost
  • Flexible custom design available
  • FAT witness test, on-site or online inspection supported

Quality Control

All measuring instruments are calibrated annually. Each component goes through strict inspection as below:

PartInspection Items
Coil1. Raw material physical & chemical test2. Winding process audit3. Winding dimension check
Iron Core1. Silicon steel material test report2. Lamination burr and paint film inspection3. Stack dimension check
Frame1. Welded component qualification certificate2. Finishing dimension inspection
Rotor1. Core stacking inspection2. Rotor bar welding inspection3. Bar & end ring material, appearance, conductivity and dimension test4. Slot bar fastening check5. Outer diameter and core dimension inspection6. Dynamic balancing
Shaft1. Raw material and annealing inspection2. Finishing inspection
Stator1. Core compression check2. Core length and segment length check3. Winding insertion inspection4. Iron loss test
Assembly1. Plain bearing dimension and surface quality check2. Air gap, stator-rotor alignment, fan and shroud clearance check3. Internal cleaning inspection4. Shaft center height and mounting dimension verification
Test1. Routine test2. Type test

Test Items

Every motor is fully tested before shipment and supplied with an official test report after passing.

  • Routine test: Winding DC resistance, insulation resistance, high voltage withstand, no-load current, no-load power, no-load loss, three-phase current unbalance, locked rotor current, locked rotor torque, maximum torque, rotation direction, vibration (horizontal / vertical / axial), noise
  • Type test: Full-load input power, full-load current, stator loss, rotor loss, iron loss, mechanical loss, stray loss, slip, winding temperature rise, bearing temperature, hot insulation resistance, overload test, power factor, efficiency

After Sales Service

Warranty Terms

Standard warranty: 12 months after commissioning or 18 months after delivery, whichever comes first. Extended warranty can be negotiated upon request.


0